      "title": "Photovoltaic System Fire Risk",
      "shortDefinition": "Photovoltaic systems carry a specific fire risk from DC components, wiring and module mounting structures that, especially on roof-mounted arrays, affects both firefighting access and property protection of the building.",
      "synonyms": [
        "PV fire risk",
        "Solar system fire"
      ],
      "linesOfBusiness": [
        "Property",
        "Engineering"
      ],
      "jurisdictions": [
        "CH",
        "EU",
        "Global"
      ],
      "tags": [
        "Fire protection",
        "Renewable energy"
      ],
      "relations": {
        "relatedTerms": [
          "riskg-electrical-installations",
          "riskg-lithium-ion-batteries",
          "riskg-roofing-systems-fire"
        ],
        "partOf": [],
        "appliesTo": [
          "cov-photovoltaikversicherung",
          "cov-property-all-risks"
        ],
        "regulatedBy": [],
        "relevantFor": [],
        "insurableVia": [],
        "mitigatedBy": [],
        "comprises": [],
        "alternativeTo": [],
        "complementedBy": []
      },
      "attribute": null,
      "profile": null,
      "coverageProfile": null,
      "clause": null,
      "legalBasis": [],
      "standards": [
        "VdS 3145 – Photovoltaic Systems",
        "VdS 6023 – Rooftop Photovoltaic Installations, Options for Minimising Fire Risk"
      ],
      "reviewStatus": "expert-reviewed",
      "reviewedBy": "Guido Hesse, Hesse Group Holding AG",
      "lastReviewed": "2026-09-04",
      "version": "0.1.0",
      "updated": "2026-09-01",
      "generated": {
        "by": "cursor-agent/claude-sonnet-5",
        "at": "2026-09-01T00:00:00.000Z"
      },
      "verified": [
        {
          "by": "human:ghesse",
          "at": "2026-09-04T00:00:00.000Z",
          "method": null
        }
      ],
      "staleAfter": null,
      "url": "https://hgh.ch/lexikon/en/knowledge/risk-engineering/photovoltaic-fire-risk/",
      "alternateUrl": "https://hgh.ch/lexikon/de/wissen/risk-engineering/photovoltaik-brandrisiko/",
      "body": "## Hazard picture\n\nUnlike faults in conventional AC installations, DC-side arc faults in PV strings do not necessarily trip protection because there is no zero crossing; they can smoulder undetected for hours. Additional risk sources include substandard connectors, thermally overloaded cables underneath the module surface, rodent damage and installation errors in the mounting structure. On roofs, modules and wiring also complicate firefighting, since live conductors pose a hazard to fire crews.\n\n## Protective measures\n\nKey measures are proper design and testing of the DC side including arc-fault detection, fire-safe spacing between module fields to preserve escape routes and firefighting access, and recurring inspection under recognised regimes including thermographic scanning and I-V curve measurement. For existing roofs, the compatibility of PV loading with the roof waterproofing and the fire resistance of the roof construction must be verified.\n\n## Insurance relevance\n\nFor standalone photovoltaic insurance and property insurance of the building, documentation of the commissioning test and recurring inspections is a key criterion for risk classification. Missing clearances to combustible roof structures or unclear separation from battery storage are treated as aggravating risk factors."
    },
    "de": {
      "id": "riskg-photovoltaic-fire-risk",
      "lang": "de",
      "type": "risk-guideline",
      "title": "Brandrisiko von Photovoltaikanlagen",
      "shortDefinition": "Photovoltaikanlagen bergen durch Gleichstromkomponenten, Verkabelung und Modulunterkonstruktion ein spezifisches Brandrisiko, das insbesondere bei Dachanlagen die Bekämpfung und den Sachschutz des Gebäudes beeinflusst.",
      "synonyms": [
        "PV-Brandrisiko",
        "Solaranlagenbrand"
      ],
      "linesOfBusiness": [
        "Sach",
        "Technische Versicherung"
      ],
      "jurisdictions": [
        "CH",
        "EU",
        "Global"
      ],
      "tags": [
        "Brandschutz",
        "Erneuerbare Energien"
      ],
      "relations": {
        "relatedTerms": [
          "riskg-electrical-installations",
          "riskg-lithium-ion-batteries",
          "riskg-roofing-systems-fire"
        ],
        "partOf": [],
        "appliesTo": [
          "cov-photovoltaikversicherung",
          "cov-property-all-risks"
        ],
        "regulatedBy": [],
        "relevantFor": [],
        "insurableVia": [],
        "mitigatedBy": [],
        "comprises": [],
        "alternativeTo": [],
        "complementedBy": []
      },
      "attribute": null,
      "profile": null,
      "coverageProfile": null,
      "clause": null,
      "legalBasis": [],
      "standards": [
        "VdS 3145 – Photovoltaikanlagen",
        "VdS 6023 – Photovoltaik-Anlagen auf Dächern, Möglichkeiten zur Minimierung eines Brandrisikos"
      ],
      "reviewStatus": "expert-reviewed",
      "reviewedBy": "Guido Hesse, Hesse Group Holding AG",
      "lastReviewed": "2026-09-04",
      "version": "0.1.0",
      "updated": "2026-09-01",
      "generated": {
        "by": "cursor-agent/claude-sonnet-5",
        "at": "2026-09-01T00:00:00.000Z"
      },
      "verified": [
        {
          "by": "human:ghesse",
          "at": "2026-09-04T00:00:00.000Z",
          "method": null
        }
      ],
      "staleAfter": null,
      "url": "https://hgh.ch/lexikon/de/wissen/risk-engineering/photovoltaik-brandrisiko/",
      "alternateUrl": "https://hgh.ch/lexikon/en/knowledge/risk-engineering/photovoltaic-fire-risk/",
      "body": "## Gefährdungsbild\n\nAnders als bei klassischen Elektroinstallationen führen gleichstromseitige Fehlerlichtbögen in PV-Strängen nicht zwangsläufig zur Abschaltung, da kein Nulldurchgang existiert; sie können unbemerkt über Stunden brennen. Zusätzliche Risikoquellen sind mangelhafte Steckverbinder, thermisch überlastete Kabel unter der Modulfläche, Tierverbiss und Montagefehler an der Unterkonstruktion. Auf Dächern erschweren Module und Verkabelung zudem die Brandbekämpfung, weil unter Spannung stehende Leitungen für die Feuerwehr eine Gefahr darstellen.\n\n## Schutzmassnahmen\n\nWesentliche Massnahmen sind eine fachgerechte Auslegung und Prüfung der Gleichstromseite einschliesslich Lichtbogenerkennung, brandschutzgerechte Abstände zwischen Modulfeldern zur Bildung von Rettungswegen und Löschzugängen, sowie eine wiederkehrende Inspektion nach anerkannten Prüfregimes einschliesslich Thermografie und I-U-Kennlinienmessung. Für Bestandsdächer ist die Verträglichkeit von PV-Auflasten mit der Dachabdichtung und dem Feuerwiderstand der Dachkonstruktion zu prüfen.\n\n## Versicherungsrelevanz\n\nFür die eigenständige Photovoltaikversicherung und die Sachversicherung des Gebäudes ist die Dokumentation der Inbetriebnahmeprüfung und der wiederkehrenden Inspektionen ein wesentliches Kriterium der Risikoeinstufung. Fehlende Abstände zu brennbaren Dachaufbauten oder unklare Trennung zu Batteriespeichern gelten als erschwerende Risikofaktoren."
    }
  }
}